Badger Meter SRD/SRI Valve Positioners User Manual

Page 13

Advertising
background image

SRD960 with communication PROFIBUS-PA and FOUNDATION Fieldbus H1
SRD960-xPxxxx or SRD960-xQxxxx

PROFIBUS-PA

Data transfer . . . . . . . . . . . . according to PROFIBUS- PA

profile class B based on EN

50170 and

DIN 19245 part 4

GSD file . . . . . . . . . . . . . . . . the actual file can be down-

loaded from our

homepage

Configuration

Local / Display . . . . . . . . . . . see “Functional Specifications

Software . . . . . . . . . . . . . . . VALcare™ (FDT-Software)
Hardware. . . . . . . . . . . . . . . PC- or PCMCIA-interfaces

from Softing

I/A Series System . . . . . . . . with FBM223
Other control systems . . . . . All Profibus-PA- compatible,

e.g. Siemens SIMATIC PDM

(ProcessDevice Manager)

FOUNDATION Fieldbus H1

Data transfer . . . . . . . . . . . . according to Fieldbus

FOUNDATION Specification

Rev. 1.4, Link-Master (LAS).

Function Blocks . . . . . . . . . . AO, Transducer, Resource,

PID, 2xDI, DO

DD files . . . . . . . . . . . . . . . . the actual file can be down-

loaded from our

homepage

Configuration

Local / Display . . . . . . . . . . . see “Functional Specifications

Software . . . . . . . . . . . . . . . VALcare™ (FDT-Software)

or National Instruments

NI-FBUS configurator

Hardware. . . . . . . . . . . . . . . FBUS-interfaces (AT-FBUS

and PCMCIA- FBUS)

I/A Series System . . . . . . . . with FBM220 / 221
Other control systems . . . . . All Fieldbus FOUNDATION

H1-compatible.

Fisher Rosemount Delta-V,

Honeywell, Yokogawa, ABB

*)

Data of ”Intrinsically Safe” version

For both fieldbus versions

Input signal . . . . . . . . . . . . . digital
Supply voltage . . . . . . . . . . . DC 9 to 32 V *)
max. Supply voltage. . . . . . . DC 48 V
Operating current . . . . . . . . . 10.5 mA ± 0.5

(base current)

Current amplitude . . . . . . . . ± 8 mA
Fault current. . . . . . . . . . . . . base current + 0 mA

(base current + 4 mA by means of independent

FDE-safety circuit) according to IEC 1158-2

Start-up time (init phase) . . . approx. 2 sec

Operating values
Bus connection . . . . . . . . . . Fieldbus interface based

on IEC 1158-2 according to FISCO-Model

(see Electrical certifications)

Power supply . . . . . . . . . . . . Power supply is achieved

dependant on the application by means of fieldbus

power supply units or segment coupler

(common data for SRD960 -B or C)”,

Operation and configuration

(common data for SRD960 -B or C)”,

Operation and configuration

POS-UM-00012-EN-02

Physical Specifications (Common Data for SRD960-B,-C or -T)

Page 13

August 2014

Advertising