Badger Meter SRD/SRI Valve Positioners User Manual

Page 14

Advertising
background image

SRD960 as Position Transmitter stand
alone unit SRD960 -TxQ

Input . . . . . . . . . . . . . . . . . Stroke / Rotary angle by

means of conductive

plastic precision

potentiometer

Output . . . . . . . . . . . . . . . . Two wire system
Signal range . . . . . . . . . . . . 4 to 20 mA / 20 to 4 mA

or free configuration

3.8 to 20.5 mA

Permitted load . . . . . . . . . . . R

bmax

= (Us–12 V) / 0.02 A [

Ω]

(Us = supply voltage)

Power supply
Reverse polarity protection . . standard feature
Supply voltage . . . . . . . . . . . Us = DC 12 to 36 V
Permitted ripple . . . . . . . . . . < 10 % p.p.
Supply voltage dependency . negligible

Response characteristic
Non-linearity (terminal
based adjustment) . . . . . . . . < 1% F.S.
Hysteresis . . . . . . . . . . . . . . < 0.5% F.S.
Load dependency . . . . . . . . negligible
Temperature effect. . . . . . . . < 0.1 % / 10 K

Weight . . . . . . . . . . . . . . . . . approx. 2.3 kg

Configuration and status
Local configuration . . . . . . . . 2 push buttons and 2 LEDs

SRD960 as potentiometer unit for remote
mounting application
SRD960 -Txxxx - H

Travel Range
Stroke range . . . . . . . . . . . . 8 to 260 mm (0.3 to 10.2 in)
with standard feedback levers; special levers on request
Rotation angle range . . . . . . up to 95 ° (to 300° on request)

(without mechanical stop)

Response Characteristic
please refer you to the technical data of the positioner

SRD960 with which is mounted together.

Weight . . . . . . . . . . . . . . . . . approx 2.3 kg

Ambient conditions
Ambient temperature . . . . . . –40 to 100 °C (–40 to 212 °F)
IP66
For more information about remote mounting please

consult

TI EVE0105_R

.

OPTION for all SRD960 -B or C

Pressure sensors

[item

3

]

Three built-in pressure sensors, Code "Option –B”,

for supply air, output y1 and y2 to actuator,

necessary for Premium Diagnostic

Measuring range . . . . . . . . . 0 to 8 bar (0 to 120 psig)
Accuracy . . . . . . . . . . . . . . . 0.5 %
Temperature influence . . . . . 0.5 % / 10 K (–40 to 80 °C)

Parts set for subsequent mounting:
Option B (3x pressure sensors) . . . . . EW 426 247 311

Option –B “Built-in pressure sensors”

POS-UM-00012-EN-02

Physical Specifications (Common Data for SRD960-B,-C or -T)

Page 14