Badger Meter SRD/SRI Valve Positioners User Manual

Page 8

Advertising
background image

Features

Automatic start-up . . . . . . . . Autostart functionality

Automatic detection of mechanical stops, control

parameters and of direction of spring force. A dynamic

optimization is included in this procedure. This procedure

allows a full adaptation on optimi- zation of the positioner

to the actuator without any manual adjustments!

Options

Built-in independent inductive limit switches

Pressure Sensors for supply air pressure and output

pressure I (y1) and II (y2)

Additional Inputs / outputs:

2 binary outputs (position alarms)

Position feedback 4 to 20 mA + binary alarm output

2 binary inputs

Operation and configuration

Local . . . . . . . . . . . . . . . . . . with four keys
Display. . . . . . . . . . . . . . . . . Multi-Lingual Graphic LCD

or five LEDs

The positioner in LCD version is available with three

different menu languages:
Two menu languages are standard:
- English
- German

Freely definable third language (additional languages on

request):
- French

- Portuguese

- Spanish

- Italian

- Swedish

- etc.

The third menu language has to be selected and specified

with order.
All additional Menu languages can be downloaded into the

positioner by means of the operation- and configuration

software VALcare™. Additional language

downloads

are

available on our homepage.

Position feedback and alarms

Position feedback / valve position . . via communication

Optional

1)

. . . . . . . . . . . . . 4 to 20mA position feedback

Alarms . . . . . . . . . . . . . . . . . via communication

Optional

1)

. . . . . . . . . . . . . 1 alarm output

Position alarms . . . . . . . . . . via Kommunikation

Hi and Lo alarm

Hi/Hi and Lo/Lo alarm

Optional

1)

. . . . . . . . . . . . . 2 binary outputs

Hi and Lo alarm

Hi/Hi and Lo/Lo alarm

Independent feedback:
Limit switch (inductive) . . . . . Standard version

Security version

1) By means of additional inputs/outputs (Option Board)

Diagnosis

– local

Self diagnostics

Status- and diagnostic messages

– via VALcare™ Valve Diagnostic Software:

Service Management for planning and scheduling of

service intervals

Histograms for displaying the position- and response

history over time

Partial Stroke Test for the functional inspection of sa-

fety related actuators

Hours in operation, cycle counter and travel sum of

the actuator are determined

Surveillance of loop current

shows condition of device:

- Potentiometer

- IP Motor

- exceeding range of actuator (possible indication for

wear of plug or seat)

- remaining control deviation (possible indication for

jammed actuator, blocked valve stem or plug, not

sufficient air capacity /supply air pressure /positioning

pressure)

• if equipped with pressure sensors (optional):

• Monitoring of the stem friction

• Histograms for displaying the friction-history

over time

• surveillance of air supply and output pressure,

each with display of physical value

• Additional diagnostical possibilities in control

operation by means of external sensors (optional).
See also the VALcare™ Documentation.

Service plug and IrCom

All basic devices are equipped with a service plug

A at the

front side. There via RS232 interface a PC with VALcare™

(DTM) can be connected via modem EDC82 (galv.

separated, not Ex).
Information about EDC82 modem see

TI EVE0102_Y

.

If the SRD is equipped with option “IrCom”

B , communication

can take place contactless via infrared with the positioner

(even with a closed cover!). A modem “IR Interface” (not

Ex) connected via RS232 interface to a PC with VALcare™

(DTM) makes communcation possible up a range of

approx. 0,5 m.
(If the notebook has an IrDa interface, this cannot be used

despite being similartechnology as IrDa instruction set has

no communication commands for positioners.)

POS-UM-00012-EN-02

Functional Specifications (Common Data for SRD960-B or -C)

Page 8

August 2014

Advertising