Additional equipment, Additional equipment 15 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 15

Advertising
background image

ADDITIONAL EQUIPMENT

Additional Inputs / Outputs, built into any SRD960 -B or C

Order in Model Code: SRD960–

P

Order in Model Code: SRD960–

Q

Two binary outputs

(limit signals) [item

1

]

Stroke / angle derivated from positioner feedback,
configurable
galvanically separated 2 limit signals, two-wire system,

according to DIN 19234, for external supply

supply voltage . . . . . . . . . . DC 8 to 48 V
Logic:

limit value not exceeded . . . < 1 mA
limit value exceeded . . . . . > 2.2 mA (typ. 6 mA)
device fault . . . . . . . . . . . < 50

µA

configurable as switch output:

limit value not exceeded . . . < 50

µA

limit value exceeded . . . . . > 20 mA / 20 V

> 40 mA / 10 V

(power derated)

Reference: AB1 for upper, AB2 for lower limit
Terminals for AB1 . . . . . . . . 81+, 82–

AB2

83+, 84–

Explosion protection thereto see “PHYSICAL
SPECIFICATIONS.”

Parts set for subsequent mounting:
Code P . . . . . . . . . . . . . . . . EW 426 346 021

Position feedback 4 to 20 mA [item

1

]

Stroke / angle derivated from positioner feedback,
1 output analog, galvanically separated, two-wire system

according to DIN 19234, for external supply

supply voltage. . . . . . . . . . DC 8 to 48 V
signal range . . . . . . . . . . . 3.8 to 21.5 mA
0 % and 100 % configurable
device fault . . . . . . . . . . . . < 1 mA
Terminals for AI1 . . . . . . . 31+, 32–

1 Binary output alarm, galvanically separated, two-wire

system, according to DIN 19234, for external supply

supply voltage. . . . . . . . . . DC 8 to 48 V
Logic . . . . . . . . . . . . . . . . no alarm < 1 mA

alarm > 2.2 mA
device fault < 50

µA

Terminals for AB1. . . . . . . . 81+, 82–

The binary output for Alarm will be activated in the following

cases:
- Remaining control deviation
- Circuit to I/P module is disturbed
- Circuit to potentiometer is disturbed
- Calibration error:

- no angle calibration
- no current calibration

- Autostart failed
(Pre-settings can be configured via communication)

Explosion protection thereto see “PHYSICAL

Parts set for subsequent mounting:
Code Q . . . . . . . . . . . . . . . . EW 426 346 039

SPECIFICATIONS.”

POS-UM-00012-EN-02

Additional Equipment

Page 15

August 2014