The home display – Dwyer MPCJR User Manual

Page 10

Advertising
background image

INDEX & DOWN ARROW: Pressing these keys simultaneously
will allow backing up one menu item, or if at the first menu item they
will cause the display to return to the primary menu. If an alarm
condition has occurred, these keys may be used to reset the alarm.

INDEX & ENTER: Pressing these keys simultaneously and holding
them for 5 seconds allows recovery from the various error messages.
The following menu items will be reset:

ALiH: Alarm inhibit
CHEC CAL : Check calibration error

Correct the problems associated with the above conditions before using these
reset keys. More than one error could be present. Caution is advised since
several items are reset at one time.

The Home Display

The home display is the normal display while the control is operating. If no errors
or functions are active, the HOME display will indicate the Process Variable (the
level that is being measured) on the top display and the SP1H value, Pump 1 On
Set Point, on the bottom display.

Error messages may over-ride the HOME display. See ERROR MESSAGES on
pages 21 and 22.

While in the Secondary Menu, if no key is pressed for a period of 30 seconds, the
display will return to the HOME position displaying the process value. While in the
Secure Menu, if no key is pressed for a period of 60 seconds, the display will return
to the HOME position displaying the process value. Outputs are disabled (turned
off) when the Secure Menu is active.