WIRING FOR 485 AND 232 SERIAL COMMUNICATION OPTIONS

Wire power and outputs as shown on page 5. Wiring for options is shown in Figure
4 below. All wiring shown below is Class 2. Shielded twisted pair is recommended
for Option 485.

DO NOT run signal wiring in the same conduit or chase as the
power wiring. Erratic operation or damage to the control
circuitry will result.

Figure 4 – Wiring for Options

10

9

8

7

27 28 29

30 31 32

20

19

18

17

6

5

4

3

2

1

21 22 23

24 25

26

16

15

14

13

12

11

Terminal 29 30 31 32

Option 485 Y (receive -) Z (receive +) A (transmit -)* B (transmit +)*

Option 232 not used data out data ground data in

*For half-duplex operation wire only A and B. Do not connect to Y and Z.