SCAL

Scale Low: Select 100 to 9999 counts below SCAH. The total span
between SCAL and SCAH must be within 11998 counts. Maximum setting
range is - 1999 to + 9999 counts. Factory Default is - 5.7.

SCAH

Scale High: Select 100 to 9999 counts above SCAL. The total span
between SCAL and SCAH must be within 11998 counts. Maximum setting
range is - 1999 to + 9999 counts. Factory Default is 23.1.

S P L

Set Point Low: Select from the lowest input range value to SPH value. This
will set the minimum SP1L or SP2L value that can be entered. The value
for SP1L or SP2L will stop moving when this value is reached. Factory
Default is -5.7.

SPH

Set Point High: Select from the highest input range value to SPLvalue. This
will set the maximum SP1H or SP2H value that can be entered. The value
for SP1H or SP2H will stop moving when this value is reached. Factory
Default is 23.1.

S1St

Set Point 1 State: Select P in or POut. Factory default is POut.

P in

Pump In (Direct Action). As the input increases the output
will increase.

POut

Pump Out (Reverse Action). As the input increases the output
will decrease.

5ILP

P1 Lamp: Select 0 on or OoFF. Factory default is 0 on.

0 on

Lamp ON when Output is ON.

OoFF

Lamp OFF when Output is ON.

S2St

Set Point 2 State: Select P In, POut or OFF. Factory default is POut.

P in

Pump In (Direct Action). As the input increases the output
will increase.

POut

Pump Out (Reverse Action). As the input increases the output
will decrease.

52LP

P2 Lamp: Select 0 on or OoFF. Factory default is 0 on.

0 on Lamp ON when Output is ON.
OoFF Lamp OFF when Output is ON.