Programmimg example example programming chart – Dwyer MPCJR User Manual

Page 26

Advertising
background image

25

Example:
• Keep Empty, two pump

(duplex)

• Depth 25 feet
• Pump 1: Start at 6 feet

Stop at 3 feet

Pump 2: Start at 12 feet

Stop at 9 feet

• Low level alarm: 1 foot,

fixed, auto reset

• High level alarm: 20 feet,

fixed, auto reset

• Want Lead/Lag function on
• No communication options
• Want 4-20 mA

retransmission

• Using with a 4-20 mA input.

PROGRAMMIMG EXAMPLE

EXAMPLE PROGRAMMING CHART

MENU

Secondary

ITEM

SPIH
SPIL

SP2H
SP2L

A1Hi

A2Lo

DEFAULT

23.1

-5.7

23.1

-5.7

23.1

2.0

SET AT

6.0
3.0

12.0

9.0

20.0

1.0

DESCRIPTION
Set Point 1 value (default is in feet)
Set Point 1 off value (default is in feet)
Set Point 2 value (default is in feet)
Set Point 2 off value (default is in feet)
Alarm 1 (high) value (default is in feet)
Alarm 2 (low) value (default is in feet)