Figure 2 - Wiring

WIRING

Do not run transmitter wiring or other Class 2 wiring in the same conduit as power
leads. Use only the probe or transmitter for which the control has been
programmed. Maintain separation between wiring of sensor, auxiliary in or out, and
other wiring. See the "Secure Menu" for input selection.

Supply connections should be made in accordance with the National Electrical
Code per Article 300, and local regulations. All line voltage output circuits must
have a common disconnect and be connected to the same pole of the disconnect.
Input wiring for probe or transmitter is rated CLASS 2.
Control wiring is as shown in Figure 2 below.

Voltage

Current

Alarm 1

Contacts

Alarms 2

Contacts

24 VDC

@ 50 mA

Isolated

Pump 1

Output

Pump 2

Output

Line Input

100 to 240 VAC

50 - 400 Hz. Single PH

132 to 240 VDC 5VA

MAX. Output Ratings:

Relay: 10A. @ 240 VAC RES.

1/4 HP @ 120 VAC

1/3 HP @ 240 VAC

Alarm: 3A. @ 240 VAC RES.

P.D. 240VA, 120/240 VAC

SW. Volt.: 15 VDC @ 20 mA

NOTE:

1. For supply connections

use No. 16 AWG or larger

wires rated for at least 75°C,
or in accordance with an

equivalent national standard.

2. Maximum ambient temperature

rating 131°F (55°C)
3. Use copper conductors only

4. Terminals 1-5, 10-12, & 21-32

are class 2 'SELV'.

15 VDC

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

32

31

30

29

28

27

21

22

23

24

25

26

N.O.

N.O.

COM.

COM.

N.O.

N.O.

N.C.

N.C.

COM.

COM.

CURRENT

RELAY

& SSR

290-3126

COM.

Pump1 Pump2

+

-

Option RV, RC