MENU SELECTIONS
Notation Conventions for the Menus

Because of the number of features available in this control, information is included
that may not apply to your specific control. All usable features are included in this
book, but may not be used in your process. To increase clarity the following
conventions are used:

1. Certain features or functions shown in this book are contextual. This means that
Menu Items may or may not appear, depending on other Menu Item selections.
Whenever this occurs, a notation is made in the Menu Item that "controls" or
"directs" other menu items. If you are looking for a particular menu item and can't
find it, check the menu item that is its "control" for proper setting.

2. The "#" symbol is used in two ways. It is used inside a group of characters to
indicate which set point function (SP1 or SP2) is being affected. It is also used
before a group of characters of a menu item to indicate that there may be more than
one selection or value for that menu item.

Secondary Menu

Press the UP ARROW and Enter keys to start the menu. Press

INDEX to advance to the next menu item. Press UP ARROW or DOWN

ARROW to change the value in the display. Press ENTER to retain the

value.

SP1H

Pump 1 On Set Point. Factory Default 23.1 (feet).

SP1L

Pump 1 Off Set Point. Factory Default -5.7 (feet).

SP2H

Pump 2 On Set Point. Factory Default 23.1 (feet).

SP2L

Pump 2 Off Set Point. Factory Default -5.7 (feet).

A1Hi

Alarm 1 High: Factory Default 23.1 (feet).

A2Lo

Alarm 2 Low: Factory Default 2.0 (feet).