Display, Sp outputs, Meaning – Dwyer MPCJR User Manual

Page 22: Action required, Diagnostic error messages

Advertising
background image

21

DISPLAY

No

display

lighted

FAIL

tESt

CHEC

LorE

SP OUTPUTS

Set point

outputs inactive

Alarms inactive

Set point

outputs inactive

Alarms inactive

Set point

outputs active

Alarms inactive

MEANING

Display is blank.
Instrument is not
getting power, or
the supply
voltage is too
low.

Fail test appears
upon power up if
the internal
diagnostics
detect a failure.
This message
may occur during
operation if a
failure is
detected.
Displays flash.

This message
appears if the
Serial
Communications
has timed out.

ACTION REQUIRED

Check that the power
supply is on, or that the
external fuses are good.

The display alternates
between FAIL tESt and
one of the following
messages: FACt dFLt:
Memory may be corrupted.
Press the ENTER key and
the DOWN ARROW key to
start the factory default
procedure. Recheck
controller programming.
rEt FACt : Unrecoverable
error, return to factory for
service.

Restore the
communications line and
switch the LorE to LOC.

DIAGNOSTIC ERROR MESSAGES