Secure Menu

Press the UP ARROW and Enter keys for 5 Seconds to start the menu.

Press INDEX to advance to the next menu item. Press UP ARROW or

DOWN ARROW to change the value in the display. Press ENTER to retain

the value. OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN

THE SECURE MENU.

SECr

Security Code: See the Security Level Selection and the Password Table

on page 10, in order to enter the correct password. Factory Default is 4.

InP

Input Type: Select one of the following. Refer to the Input wiring section for

the proper wiring. Factory Default is Curr.
Curr

DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.

UOLt

DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.

- - - - Reserved

InPC

Input Correction: Select ±500 counts. This feature allows the input value to

be changed to agree with an external reference or to compensate for
sensor error. Note: InPC is reset to zero when the input type is changed,
or when decimal position is changed.

LdLg

Lead / Lag: Select On or OFF. Factory default is On. (See page 11).

On

The Lead/Lag function is enabled. The outputs of SP1 and SP2
will alternate.

OFF

The Lead/Lag function is disabled.

OSUP

Zero Suppression: Select On or OFF. Factory default is OFF.

OFF

The input range will start at 0 (zero) Input.

On

The input range will start at 4.00 mA or 2.00 V.

dPT

Decimal Point Positioning: Select 0, 0.0, 0.00, or 0.000. All Menu items
related to the input will be affected. Factory default is 0.0.

PEA

The Peak feature stores the highest input the control has measured since

the last reset or Power On. At Power On PEA is reset to the present
input. To manually reset the value PEA must be in the lower display.
Press the ENTER key to reset. PEA will be reset and display the
present input value.

UAL

The Valley feature stores the lowest input the Controller has measured
since the last reset or Power On. At Power On UAL is reset to the present
input. To manually reset the value UAL must be in the lower display.
Press the ENTER key. UAL will be reset and display the present
input value.