12. Troubleshooting

If any malfunctions occur, refer to the following items after checking the power supply and wiring.

Indication

Phenomenon

Presumed cause and solution

” is blinking on the PV

display.

Sensor

(Thermocouple, RTD and DC voltage

[0 to 1Vdc] input) is burnt out.

Change the sensor for new one.

The lead wire of the sensor

(Thermocouple, RTD and DC

voltage [0 to 1Vdc] input ) is not securely connected.

Connect it to the terminal properly.

The indication on the PV display
does not change.

Sensor (DC current [0 to 20mAdc] and DC voltage

[0 to 10Vdc]) is burnt out.
Change the sensor for the new one.

The

lead wire of the sensor (DC current [0 to 20mAdc] and

DC voltage [0 to 10Vdc] is not securely connected to the
terminal.
Connect the sensor lead wire securely to the instrument
terminal.

” is blinking on the PV

display.

Sensor

(DC current [4 to 20mAdc] and DC voltage[1 to 5Vdc]

input) is burnt out.
Change the sensor for the new one.

The sensor lead wire is not securely connected to the

terminal (DC current

4 to 20mAdc) and DC voltage

[1 to 5Vdc]
Connect the sensor lead wire securely to the terminal of
the instrument.

The indication on the PV display

is abnormal or unstable.

Designation

of the sensor (input) is incorrect.

Set the correct sensor (input).

The

polarity of the sensor input is incorrect.

Wire it correctly.

Temperature unit (°C/°F) is mis-selected.

Set the correct unit.

AC

is leaking from controlled object to thermocouple or RTD.

Keep AC from leaking into the controlled object.

” is indicated on the

PV display.

Internal memory is out of order.

Please contact our sales branch or the shop where you

purchased this unit.

Key operation

Phenomenon

Presumed cause and solution

Setting values do not change

even if the

or

key is

pressed during setting mode

Mode1

or mode 2 is selected in setting value lock selection.

Cancel the Lock mode.

PID auto-tuning is performing.

Cancel PID auto-tuning.

Unable to set the value beyond

or below scaling high limit or low
limit within the rated scale range

even if the

or

key

is pressed.

The

value of scaling high limit setting or low limit setting in

auxiliary function setting mode 2 is set to still one.

Set the proper value.

• If you have any inquiries, please contact us or the shop where you purchased the unit.