Dwyer SCZ10 User Manual

Page 5

Advertising
background image

Character

Name, Description, Setting range

Initial value

Heate r burnout alarm setting

• Sets the heater current value for

Heater burnout alarm.

•

Setting the value to 0.0 disables this function.

• Self-holding is not available for the alarm output.

When

alarm and Loop break alarm are applied together,

the output is common.

•

This setting item is not indicated when [Option: W] is not added.

• Rating

5A : 0.0 to 5.0A

Rating

20A: 0.0 to 20.0A

Rating

10A: 0.0 to10.0A

Rating

50A: 0.0 to 50.0A

0.0A

Loop break alarm time setting

• Sets the time to assess the Loop break alarm.
• Setting the value to

0 disables this function.

• When

alarm and Heater burnout alarm are applied together,

the output is common.

•

0 to 200 minutes

0 minutes

Loop break alarm action span setting

• Sets the action span to assess the Loop break alarm.
• Setting the value to

0 disables this function.

• When

alarm and Heater burnout alarm are applied together,

the output is common.

•

Thermocouple and RTD input

0 to 150 ( ) or 0.0 to 150.0 ( )

DC voltage and DC current input

0 to 1500 (Decimal point place follows the selection)

0°

(Table 3.3-1)

Alarm action type

Setting range

High limit alarm

-(Scaling span) to Scaling span

Low limit alarm

-(Scaling span) to Scaling span

High/Low limits alarm

0 to Scaling span

High/Low limit range alarm

0 to Scaling span

Process high alarm

Scaling low limit setting value to high limit value

Process low alarm

Scaling low limit setting value to high limit value

High limit alarm w/standby

-(Scaling span) to Scaling span

Low limit alarm w/standby

-(Scaling span) to Scaling span

High/Low limits w/standby

0 to Scaling span

-side minimum

setting value

-199.9 or -1999

+side maximum

setting value

999.9 or 9999

3.4 Auxiliary function setting mode 1

Character

Name, Description, Setting range

Initial value

Setting value LOCK designation

• Locks

the setting value to prevent setting errors.

The setting item to be locked is dependent on the designation.

• PID

auto-tuning cannot be carried out when Lock1 or Lock2

is selected.

•

(Unlock): All setting values can be changed.

(LOCK 1): None of setting values can be changed.
(LOCK 2): Only main setting mode can be changed.

Unlock

(LOCK 3): All setting values can be changed except Controller/Converter

function selection. However they return to their former value
after power is turned off because they are not saved in the
non-volatile memory. (Be sure to select LOCK 3 when using
with PC-900 [SVTC attached])