Dwyer SCZ10 User Manual

Page 7

Advertising
background image

Character

Name, Description, Setting range

Initial value

PV filter time constant setting

• Sets the

PV filter time constant.

If the setting value is too large, it affects control result due to

the response delay.

•

0.0 to 10.0 seconds

0.0 seconds

Control output high limit setting

• Sets the control output high limit value.
• This setting item is not indicated when

ON/OFF action.

• Control output low limit

to 105%

Setting greater than 100% is effective to DC current output type

100%

Control output low limit setting

• Sets the control output low limit value.
• This

setting item is not indicated during ON/OFF action.

•

-5% to control output high limit

Setting less than 0% is effective to DC current output type.

0%

Control output ON/OFF action hysteresis setting

• Sets the

ON/OFF action hysteresis for the control output.

•

This setting item is indicated only for ON/OFF action (P=0)

•

Thermocouple and RTD input: 0.1 to 100.0°C (°F)

DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)

1.0°C

Alarm action selection

• Selects alarm action type.

No alarm

:

High limit alarm

:

Low limit alarm

:

High/Low limits alarm

:

High/Low limit range alarm

:

Process high alarm

:

Process low alarm

:

High limit alarm w/standby

:

Low limit alarm w/standby

:

High/Low limits alarm w/standby :

No alarm

Alarm action Energized/Deenergized

• Selects alarm action Energized/Deenergized.
•

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

•

Energized:

Deenergized:

Energized

Alarm HOLD function selection

• Selects whether alarm HOLD function is [Used] or not.

If alarm HOLD function is set to used, once the alarm
functions alarm output remains until the power is turned off.

•

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

• Alarm

HOLD [Not used]:

Alarm

HOLD

[Used]

:

Alarm HOLD
[Not used]

Alarm hysteresis setting

• Sets the alarm hysteresis.
•

This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].

•

Thermocouple and RTD input

: 0.1 to 100.0°C (°F)

DC voltage and DC current input: 1 to 1000 (Decimal point
place follows the selection.)

1.0°C