Dwyer SCZ10 User Manual

Page 4

Advertising
background image

3.2 Main setting mode

Character

Name, Description, Setting range

Initial value

Main setting

• Set the value for controlled objects.
•

Scaling low limit setting value to Scaling high limit setting value

(Decimal point place follows the selection for DC current input)

0° C

3.3 Sub setting mode

Character

Name, Description, Setting range

Initial value

PID auto-tuning Perform/Cancel

• Performs

PID auto-tuning. However when PID auto-tuning does

not finish after 4 hours it started, PID auto-tuning is shut down
compulsory.

•

PID cancellation

:

PID auto-tuning performing:

Proportional band setting

• Sets the p

roportional band.

•

ON/OFF action when setting the value to 0.0

•

0.0 to 110.0%

2.5%

Integral time setting

• Sets the

integral time.

•

Setting the value to 0 disables this function.

• This

setting item is not indicated for ON/OFF action.

•

0 to 1000 seconds

200 seconds

Derivative time setting

• Sets the derivative time.
•

Setting the value to 0 disables this function.

• This

setting item is not indicated for ON/OFF action.

•

0 to 300 seconds

50 seconds

Anti-reset windup setting

• Sets

anti-reset windup.

•

Setting the value to 0 disables this function.

• This

setting item is indicated only for PID action.

•

0 to 100%

50%

Proportional cycle setting

• Sets the proportional cycle value for the control output

(OUT).

• This

setting item is not indicated for ON/OFF action or DC

current output.

•

1 to 120 seconds

Relay: 30 Sec.
Solid State: 3 Sec.

Manual reset setting

• Sets the resetting value manually.
• This

setting item is indicated only for P and PD action.

•

Proportional band converted value (In the case of DC voltage

and current input, decimal point place follows the selection.)

0.0

Alarm setting

• Sets the action point for the alarm output.
•

Setting the value to 0 or 0.0 disables this function.
(excluding Process high and Process low alarm)

When Loop break alarm and Heater burnout alarm are applied
together, the output is common.

•

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

•

See (Table 3.3-1). (In the case of DC voltage and DC current
input, decimal point place follows the selection.)

0° C