Noby UK Noby-220iR2 2-Zone User Manual

Page 12

Advertising
background image

Noby-220iiiiR2 Installation Manual

Page 12

Software Revision1-0

-

-

-

iiii

nterLink Remote Alarm 60s Delay

- Programmable Option

As supplied from the factory all fire alarms signalled across the interlink data bus are delayed by 60s to help
reduce nuisance alarms at connected properties.

Engineer Access Code-1

Select

Toggle

Relay Option

LEDs Off= iiiiLink Instant Alarm
LEDs On= iiiiLink 60s Alarm Delay*

* Factory default setting

• The green Power LED flashes rapidly upon successfully entering the Engineer Access Code.

• The LEDs surrounding button

indicate the current option status.

• Toggle button

to set/unset the desired option.

• Press

to accept OR press

to quit without updating the option.

1

1

2

2

2

2

2

2

2