System leds - interpretation – Noby UK Noby-220iR2 2-Zone User Manual

Page 23

Advertising
background image

Noby-220iiiiR2 Installation Manual

Page 23

Software Revision1-0

-

-

-

System LEDs - Interpretation

LED Label

Description

Status

Interpretation

Power
(green)

a) steady on
b) off
c) 1 blink / 4s
d) rapid flash

230VAC Mains OK
230VAC Mains Loss
230VAC Mains Restored (memory)
Code entered - awaiting a command key

Common Fire
(red)

a) steady on

b) pulsing

Local fire on Zone-1 or Zone-2

Fire alarm signalled from a remote panel
(the pulse count indicates the address no)

Common
Fault
(yellow)

a) steady on


b) 1 flash / 4s
c) 2 flash / 4s

All local panel zone & sounder circuit faults, Fault
I/P, remote panel and iiiinterlink bus faults.
Accompanied by one or more secondary fault
LEDs which identify the specific fault condition.

230VAC Mains Loss
Battery Low Voltage (pending Final Voltage)

LED Label

Description

Status

Interpretation

PSU

PSU Fault
(yellow)

a) 1 flash / 4s
b) 2 flash / 4s
c) 3 flash / 4s
d) 4 flash / 4s

230VAC Mains Loss (real time status)
PSU Low Volts (latched memory)
PSU Charger Fault
Battery O/C, Fuse F3 or Battery Ri-max fault

CPU

CPU Fault
(yellow)

a) steady on
b) 1 flash / 4s
c) 2 flash / 4s
d) 3 flash / 4s

CPU Fault (loss of comms to display PCB)
CPU Watchdog occurred (restarted OK)
Programme Memory Checksum Error
EEPROM Data Memory Checksum Error

Disablement
(yellow)

steady on

All or part of the system is disabled

Test
(yellow)

steady on

Test Mode

Latched fault conditions are cleared by performing a Panel Reset. A persistent
reoccurring fault condition could indicate a pending loss of functionality, which
should be investigated by a competent person at the earliest. If in any doubt
contact the installation company.