First power up, Connecting the detectors (figure 1), Connecting the external sounders (figure 1) – Noby UK Noby-220iR2 2-Zone User Manual

Page 7

Advertising
background image

Noby-220iiiiR2 Installation Manual

Page 7

Software Revision1-0

-

-

-

First power up

It is recommended that the Noby-220iiiiR2 is first powered up with the End Of Line devices still connected to
the screw terminal block at the panel, as supplied from the factory. This will help to establish that the panel
is functioning OK before connecting any external devices.

• Switch off or disconnect the 230VAC supply.
• Position the battery as shown in Figure-2, with the -'ve terminal to the rear of the enclosure.
• Connect the battery terminals, observing strict battery polarity.
• Press the pushbutton marked “Batt Start”.
• The panel powers up indicating a PSU fault, accompanied by a fault tone (2 beeps every 4s).
• The LED Strobe Lamp is automatically activated due to there being no 230VAC at this time.
• Switch on the 230VAC supply to the panel.
• The green Power LED blinks (occults) every 4 secs, indicating that 230VAC has been absent (memory).
• Perform a Panel Reset (refer to User Operation on page 21).
• The Noby-220iiiiR2 should now be in standby mode with a steady green Power LED and blue backlight.



Connecting the detectors
(Figure 1)

• Up to a maximum of 10 detectors can be connected to each zone.
• Up to a maximum of 10 call-points can be connected to each zone.
• Ensure that the detectors are within specification to operate at 10.5 volts.
• Use detector bases fitted with a schottky diode.
• Connect the detectors and call-points in a straight daisy-chain manner, with no spurs or loops.
• The recommended maximum cable length on each circuit is 100m.
• Maintain strict polarity from the panel, and from one detector to the next.
• Remove & re-connect the factory fitted EOLC at the outermost detector base.

Connecting the external sounders (Figure 1)

• The total combined sounder circuit current available across both circuits, is 150mA.

e.g. up to 10 sounders can be connected with a current draw of 15mA each.

• The sounders must compatible with conventional fault monitoring (polarised).
• Ensure that the sounders are within specification to operate at 10.5 volts.
• Connect the sounders in a straight daisy-chain manner, with no spurs or loops.
• The recommended maximum sounder cable length is 100m per loop.
• Maintain strict polarity from the panel, and from one sounder to the next.
• Remove & re-connect the factory fitted EOLR at the outermost sounder.