Software Revision1-0

-

-

-


LED Strobe / Lamp Output
(Terminal 5)

An external LED Strobe/Lamp can be connected between Terminal 3 (anode +'ve) and Terminal 4 (cathode
-'ve). This 12V open-collector output mimics the internal LED Strobe/Lamp and is current limited to 20mA
with an on-board 220ohm resistor.





Relay Output
(Terminal 6,7,8)

- Programmable Option

As supplied from the factory the relay operates as a Fire Alarm relay, but it can alternatively be programmed
to operate as a Fault Output Relay by keying the following sequence:

Engineer Access Code-1

Select

Toggle

Relay Option

LEDs Off= Fire Alarm Relay*
LEDs On= Fault Relay

* Factory default setting

Note that when programmed as a Fault Output the relay is normally in a de-energised state in
order to conserve standby battery power. Total power loss will therefore not be signalled to
external equipment.


• The green Power LED flashes rapidly upon successfully entering the Engineer Access Code.

• The LEDs surrounding button

indicate the current option status.

• Toggle button

to set/unset the desired option.

• Press

to accept OR press

to quit without updating the option.

1

1

2

2

2

2

1

1