Noby-220iiiiR2 Installation Manual

Page 3

Software Revision1-0

-

-

-

Noby-220iiiiR2 Overview

The Noby-220iiiiR2 Fire Control Panel is an enhanced version of the standalone Noby-220, fitted with an

iiii

nterlink data bus for connecting up to 8 control panels. Fire Alarms and Fault Warnings are signalled across

the iiiinterlink bus connection to alert neighbouring properties.

Local alarms are audibly signalled with a continuous sounder tone, whilst remotely triggered alarms are
differentiated with pulsing sounders. The origin of a fire alarm is identified on the latching LED display at all
remotely connected panels. A 60s delay on transmitted fire alarms provides a time window in which to
cancel a nuisance false alarm.

Silencing the panel-in-alarm will automatically silence all connected panels, provided that no new alarm has
been triggered from another panel. Each property owner can silence their own local sounders manually at
their panel. All panels will re-sound upon receipt of a new fire alarm. Fire alarm LED indication is latched
until a Panel Reset is performed at each individual property.

Fault LED indications remain latched at the local property until the panel is reset. Fault conditions
originating from remote properties are displayed in real-time at the local panel, and the LED indications are
automatically cleared when the remote panel is reset. Audible fault tones are only provided at the local
property.

The Noby-220iiiiR2 control panel is fully monitored according to EN54-2 and EN54-4 standards, and the

iiii

nterlink data connection is securely monitored for physical disconnection and/or data errors.