Table 10: parameter modules - input parameters – NORD Drivesystems BU0940 User Manual

Page 40

Advertising
background image

S7 standard modules

– Supplementary manual options for NORD - Frequency Inverters

40

BU 0940 GB-3612

Name

Type

Interfac
e

Description

Module Para_...

…PPO1+…

…ACYC_…

…2

R

…2

W1

6

…2

W3

2

…Rea

d

…W1

6

…W3

2

param_read

BOOL

IN

0 = Reading of parameter value is not

requested. The parameter value at the
output "value_32" does not need to be
valid.

1 = Reading of parameter is requested. This

signal may be used as a static signal.
The output bits "valid" and " busy" are
updated together with the read
command.

X

X

value_16

WORD

IN

The 16 bit numerical value for the parameter
which is to be written is entered here. For
details of which parameters have a 16 bit
numerical value, please refer to the manual
for the frequency inverter.

X

X

value_32

WORD

IN

The 32 bit numerical value for the parameter
which is to be written is entered here. For
details of which parameters have a 32 bit
numerical value, please refer to the manual
for the frequency inverter.

X

X

param_write

BOOL

IN

0 = Writing of the parameter value is not

requested.

1 = Writing of the parameter is requested.

From this signal, the module forms a
positive flank, which means that the
signal must change from 0 -> 1 for for
the parameter to be re-written.

X

X

write_RAM

BOOL

IN

0 = Writing of the parameter value is not

requested.

1 = Writing of the parameter is requested.

From this signal, the module forms a
positive flank, which means that the
signal must change from 0 -> 1 for for
the parameter to be re-written. The
parameter is only written to the RAM.

X

X

wri

te

_

EEPR

O

M

BOOL

IN

0 = Writing of the parameter value is not

requested.

1 = Writing of the parameter is requested.

From this signal, the module forms a
positive flank, which means that the
signal must change from 0 -> 1 for for
the parameter to be re-written. The
parameter is written into the EEPROM
and cannot be written an unlimited
number of times.

X

X

Table 10: Parameter modules - Input parameters