7 Technical data

Function

Specification

Voltage

3~ 380...480V, -20% /+10%, 47...63 Hz

Output voltage

3 AC 0 – supply voltage

Motor output

0,55...4kW (with 400V), depending on power of the SK 300E

Brakes voltage

Depending on voltage (180V DC at 400V~ / 205V DC at 480V~) generated by
the frequency inverter; alternatively via potential-free contact (relay)

Motor temperature monitoring

I²t-monitoring ; PTC-input

Type of vetilation

Convection

Con trol input

4x dig. input 15...30V, approx. 2mA (on M12)

2x analogue/digital input (on M12)

Control output

1x analogue/digital output 24V (on M12)

1x Relay 24V / 500mA DC

Motor temperature monitoring

PTC or bimetal switch

Interface

• InterBus

• Profibus

(optional)

• CANopen

(optional)

• AS-Interface

(optional)

• DeviceNet

(optional)

Secure galvanic insulation

Control terminals (digital inputs / outputs)

Scope of the inverter

approx. 95 %

Ambient temperature

-10°C...+50°C, without condensation

Storage and transport temperature

-20°C...+60/70°C, without condensation

Long-term storage

No later than after one year, connect this frequency inverter to the mains for
60 minutes. Maintain this cycle for the period of storage.

Type of protection

IP55 / IP66 (optional), depending on the motor used

Max. altitude of installation above sea
level

Up to 1000m:

no loss of performance

1000...4000m: 1%/ 100m loss of performance (up to 2000m surge category.

3)

2,000...4,000m: only surge category 2 is adhered to; an external surge

protection is required on the power input

Waiting time between two cycles

60 sec for all appliances in the regular operating cycle

CE, EMC

Suitable for industrial use, radio interference class A