Technical data – NORSTAT Safety Relays User Manual

Page 37

Advertising
background image

22








Technical data

►

Voltage range

SAFE 1/1.1 / SAFE 2/2.1/2.2 / SAFE S.6 / SAFE 4/4.1 / SAFE M

0,9 to 1,1 UB

RS-NAGV / RS-NAGT/T.1 / SAFE L/L.1 / SAFE L.2 / SAFE Z / SAFE IRZ.2

RS-NAGU.12 / RS-NAGU.1 / RS-NAGU.2f

RS-NAGMP/P.1 / RS-NAGA/AO

0,85 to 1,1 UB

SAFE IL1 / SAFE 5/5.1 / RS-NAGL/L.1 / SAFE ILL / SAFE Z.2 / RS-NAGZ / SAFE ILZ

SAFE X4/4.1 / RS-NAGX5 / SAFE IL2 / FI1

SAFE C1, CL, CM, CZ, SAFE TU/ TA/ TN/ TR/ TON, SAFE FLEX, FLEX T, SAFE SM

0,8 to 1,25 UB

FA1 over

ASI-Bus

►

Clearance and creeping distance

DIN EN 50178, or DIN VDE 0160 at pollution grade 2, over voltage category 3/300V

► max. switching voltage

SAFE IL2 :

12 A AC, cos φ = 1

RS-NAGMP/MP.1 :

8 A AC, cos φ = 1; 8 A DC, τ =0

SAFE IRZ.2, SAFE 1/ 1.1/ 4/ 4.1/ M:

5 A AC, cos φ = 1; 5 A DC, τ =0

SAFE IL1, SAFE IL L, SAFE IL Z, RS-NAGV:

4 A AC, cos φ = 1; 4 A DC, τ =0

RS-NAGU.2f:

6 A DC (1 Kontakt), τ = 0

RS-NAGU.1/RS-NAGU.12:

1,5 A DC (1 Kontakt), τ = 0

SAFE C1, SAFE CL, SAFE CM, SAFE CZ:

1,8 A DC

Other :

6 A AC, cos φ = 1; 6 A DC, τ =0

► Protection classes

Space requirements :

IP 54

Housing :

IP 40

Terminal area :

IP 20

► Mechanical life time

10

7

switching cycles

► Electronical life time

10

5

switching cycles

► Mounting

DIN rail EN 50022 ( 35 mm )

Pay attention to housing with detachable terminal strips: if you would like to detach the terminal strips please take away the power first.

►

The ground wire has to be connected to terminal PE when an auxillary voltage used (at the terminals A1 and A2) UB~ / whit galvanic

disconnection to connect a protective conductor. By AC/DC or DC - devices is this not permitted.

All operating instructions can be found under www.automation-safety.com

Developement

Production

Special advantages
► emergency stop according to EN60204
► redundant positiv guided relay
► cyclical monitoring of the function
► housing with detachable terminal strip
(for a quick change of the devices) by the
NAG-line (without RS-NAGU.1 / RS-NAGU.2f /
RS-NAGU.1f / RS-NAGU.12)
► wireless layout
► housing of self extinguishing plastic according
to UL 94-V1
► 100% computer assisted check

Testing area

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com

Advertising