Technical data – NORSTAT Safety Relays User Manual

Page 37

Advertising
background image

22








Technical data

Voltage range

SAFE 1/1.1 / SAFE 2/2.1/2.2 / SAFE S.6 / SAFE 4/4.1 / SAFE M

0,9 to 1,1 UB

RS-NAGV / RS-NAGT/T.1 / SAFE L/L.1 / SAFE L.2 / SAFE Z / SAFE IRZ.2

RS-NAGU.12 / RS-NAGU.1 / RS-NAGU.2f

RS-NAGMP/P.1 / RS-NAGA/AO

0,85 to 1,1 UB

SAFE IL1 / SAFE 5/5.1 / RS-NAGL/L.1 / SAFE ILL / SAFE Z.2 / RS-NAGZ / SAFE ILZ

SAFE X4/4.1 / RS-NAGX5 / SAFE IL2 / FI1

SAFE C1, CL, CM, CZ, SAFE TU/ TA/ TN/ TR/ TON, SAFE FLEX, FLEX T, SAFE SM

0,8 to 1,25 UB

FA1 over

ASI-Bus

Clearance and creeping distance

DIN EN 50178, or DIN VDE 0160 at pollution grade 2, over voltage category 3/300V

► max. switching voltage

SAFE IL2 :

12 A AC, cos φ = 1

RS-NAGMP/MP.1 :

8 A AC, cos φ = 1; 8 A DC, τ =0

SAFE IRZ.2, SAFE 1/ 1.1/ 4/ 4.1/ M:

5 A AC, cos φ = 1; 5 A DC, τ =0

SAFE IL1, SAFE IL L, SAFE IL Z, RS-NAGV:

4 A AC, cos φ = 1; 4 A DC, τ =0

RS-NAGU.2f:

6 A DC (1 Kontakt), τ = 0

RS-NAGU.1/RS-NAGU.12:

1,5 A DC (1 Kontakt), τ = 0

SAFE C1, SAFE CL, SAFE CM, SAFE CZ:

1,8 A DC

Other :

6 A AC, cos φ = 1; 6 A DC, τ =0

► Protection classes

Space requirements :

IP 54

Housing :

IP 40

Terminal area :

IP 20

► Mechanical life time

10

7

switching cycles

► Electronical life time

10

5

switching cycles

► Mounting

DIN rail EN 50022 ( 35 mm )

Pay attention to housing with detachable terminal strips: if you would like to detach the terminal strips please take away the power first.

The ground wire has to be connected to terminal PE when an auxillary voltage used (at the terminals A1 and A2) UB~ / whit galvanic

disconnection to connect a protective conductor. By AC/DC or DC - devices is this not permitted.

All operating instructions can be found under www.automation-safety.com

Developement

Production

Special advantages
► emergency stop according to EN60204
► redundant positiv guided relay
► cyclical monitoring of the function
► housing with detachable terminal strip
(for a quick change of the devices) by the
NAG-line (without RS-NAGU.1 / RS-NAGU.2f /
RS-NAGU.1f / RS-NAGU.12)
► wireless layout
► housing of self extinguishing plastic according
to UL 94-V1
► 100% computer assisted check

Testing area

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com

Advertising