Comfort cool installation manual - l1_ 22, Test and running, When using the vacuum pump gas leakage check – Electrolux EXI12HD1WE User Manual

Page 22: Electrical safety check

Advertising
background image

22

When Using the Vacuum Pump

Gas Leakage Check

Test and Running

Electrical Safety Check

1

&RPSOHWHO\WLJKWHQWKHÀDUHQXWVRQ$%&
and D, connect the manifold valve charge
hose (blue) to the charge port of the low
pressure valve (3-way valve) on the gas pipe
side.

2 Connect the other charge hose (yellow) of

manifold to the vacuum pump.

3 Fully open the handle Lo of the manifold

valve.

4 Open the vacuum pump for vacuumization.

$WWKHEHJLQQLQJVOLJKWO\ORRVHWKHÀDUHQXW
of the low pressure valve to check if there
is air coming inside (If operation noise of
the vacuum pump has been changed, the
reading of multimeter is 0 instead of minus).
7KHQWLJKWHQWKHÀDUHQXW

5 Keep vacuuming for more than 15 minutes

and make sure the reading of multimeter is
[

5

Pa (-76cmHg). Then fully close

the handle Lo of manifold valve and stop the
operation of the vacuum pump.

6 Turn the stem of the stop valve B (2-way

valve) about 45° counterclockwise for 6~7
seconds after the gas coming out, then
WLJKWHQWKHÀDUHQXWDJDLQ0DNHVXUHWKH
pressure display in the pressure indicator is a
little higher than the atmosphere pressure.

7 Remove the charge hose from the low

pressure charge port.

8 Fully open the valve stems of A (3-way valve)

and B (2-way valve).

9 Securely tighten the stem cap.

1 Soap water method:

Apply soap water or liquid neutral detergent on
all valves and pipe connections (A, B, C and D,
UHIHUWRWKH¿JXUHEHORZ LQYROYHGLQLQVWDOODWLRQ
by a soft brush to check for leakage.

If bubbles come out, the pipes have leakage.

2 Leak

detector

Use the leak detector to check for leakage.

Perform the electric safe check after completing the
installation:

1 Earthing

work

$IWHU¿QLVKLQJHDUWKLQJZRUNPHDVXUHWKH
earthing resistance by visual detection and
earthing resistance tester.

2 Electrical leakage check

(performing during test running)

'XULQJWHVWRSHUDWLRQDIWHU¿QLVKLQJLQVWDOODWLRQ
the service person can use the electric probe
and multimeter to perform the electrical leakage
check. Turn off the unit immediately if refrigerant
OHDNDJHKDSSHQV&KHFNDQG¿QGRXWWKH
solution ways till the unit operate properly.

Outdoor Unit

Manifold
valve

Multimeter
-76cmHg

Lo Handle

Hi Handle

Charging hose

Low pressure
valve

Charging
hose

Vacuum Pump

Indoor unit
check points

Liquid pipe

Gas pipe

Outdoor
Unit

Outdoor unit
check points

2-way
valve

3-way
valve

B

D

C

A