Pipe Length Elevation and Additional Quantity of Gas

‡ The outdoor unit is charged with the

refrigerant for standard pipe length.

‡ When the connecting pipe length is longer

than standard length, additional refrigerant
should be added into the unit according
the above table through the service port on
3-way service valve on the outdoor unit.

‡ Please maintain the shortest distance (3 to 5

meters) and shortest misalignment possible
between the indoor and outdoor units.

‡ 7KHPD[LPXPDOORZDQFHOHQJWKDQGKHLJKW

is based on reliability.

‡ ([FHHGLQJWKHPD[LPXPPD\FDXVHSRRU

performance or malfunction.

‡ When the level difference between indoor

DQGRXWGRRUXQLWVLVJUHDWHUWKDQPD[LPXP
height, or when the outdoor unit is installed
above the indoor unit, oil trap should be
installed every 5-7 meters.

Outdoor unit

Outdoor unit

Maximum length

Maximum length

Indoor unit

Maximum height

Indoor unit

Oil trap

Rooftop Installation

1 If the outdoor unit is installed on a roof

structure, be sure to level the unit.

2 Ensure the roof structure and anchoring

method are adequate for the unit location.

3 If the outdoor unit is installed on roof

VWUXFWXUHVRUH[WHUQDOZDOOVWKLVPD\UHVXOWLQ
H[FHVVLYHQRLVHDQGYLEUDWLRQDQGPD\DOVR
be classed as non-serviceable installation.

Piping length under 5m

Piping length 5m or more

Cool

Capacity (W)

Suction Pipe

Diameter

Discharge Pipe

Diameter

Standard

Length (m)

Maximum

Length (m)

Maximum

Height (m)

Additional

Refrigerant

(g/m)

2640

Ø6.35 mm (1/4”)

Ø9.52 mm (3/8”)

5

15

5

15

3520

Ø6.35 mm (1/4”)

Ø12.7mm(1/2”)

5

15

5

15

5270

Ø6.35 mm (1/4”)

Ø12.7mm(1/2”)

5

20

10

15

6450

Ø6.35 mm (1/4”)

Ø15.88mm(5/8”)

5

20

10

15

caution

Maximum height

Advertising