Bacnet point list : ahu, Installation/owner manual 59 english – LG PQNFB17B0 User Manual

Page 59

Advertising
background image

Objects (BACnet/IP)

BACnet Point List : AHU

One AHU unit has the following 53 objects.

Point

No.

Name

ObjectName

Product Name

(XXX : Unit address)

Object

Type

Unit

Inactive

Active

Text-0

Text-1

Text-2

Text-3

Text-4

Text-5

1

ON/OFF (Setting)

StartStopCommand_XXX

BO

Stop

Start

2

ON/OFF (Status)

StartStopStatus_XXX

BI

Stop

Run

3

Lock (Setting)

LockCommand_XXX

BO

Permit

Prohibit

4

Lock (status)

LockStatus_XXX

BI

Permit

Prohibit

5

Filter Sign

FilterSign_XXX

BI

Off

On

6

Filter Sign Reset

FilterSignReset_XXX

BV

-

Reset

7

Mode (Setting)

ModeCommand_XXX

MO

Cool

Dry

Fan

Heat

8

Mode (Status)

ModeStatus_XXX

MI

Cool

Dry

Fan

Heat

9

-

-

-

10

-

-

-

11

-

-

-

12

-

-

-

13

Set Room Temperature

SetRoomTemp_XXX

AV

°C

14

Room Temperature

RoomTemp_XXX

AI

°C

15

Alarm

Alarm_XXX

BI

Normal

Abnormal

16

Error Code

MalfunctionStatus_XXX

AI

Reference LG Original Error Code

17

-

-

-

18

-

-

-

19

Set Temperature (Status)

SetTempStatus_XXX

AI

°C

20

Fire Alarm (Setting)

FireAlarmCommand_XXX

BO

Stop

Run

Installation/Owner Manual 59

ENGLISH

Advertising