26) ac humidify (setting), 27) ac humidify (status), 28) set upper temperature (setting) – LG PQNFB17B0 User Manual

Page 82: 29) set upper temperature (status)

Advertising
background image

Detailed Explanation of Object

26) AC Humidify (setting)

Point number: 25
Object name: HrvHumidifyCommand_XXX (XXX: DXHRV unit address)
Object type: Binary Output
Meaning: This object is used to set the A/C humidify status of the DXHRV.
Present_Value property:
ACTIVE: ON command
INACTIVE: OFF command

27) AC Humidify (status)

Point number: 26
Object name: HrvStartStopStatus_XXX (XXX: DXHRV unit address)
Object type: Binary Input
Meaning: This object is used to monitor the A/C humidify status of the DXHRV.
Present_Value property:
ACTIVE: ON
INACTIVE: OFF

28) Set Upper Temperature (setting)

Point number: 27
Object name: SetUpperTempCommand_XXX (XXX: A/C unit address)
Object type: Analog Value
Meaning: This object is used to set the upper temperature for the air conditioner.
Present_Value property:
Temperature(°C)
Remarks:
1. This unit is for indoor units only, and the approximate set upper temperature range is 18 ~ 30°C.
1°C is detected.

29) Set Upper Temperature (status)

Point number: 28
Object name: SetUpperTempStatus_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor set upper temperature which the indoor unit is placed.
Present_Value property:
Temperature(°C)
Remarks: This object is for indoor units only, and reports the set upper temperature data

measured by the indoor units.

82 BACnet Gateway