Objects (Modbus-TCP)

Objects (Modbus-TCP)

Supported Function Code

Monitoring and controlling items of air conditioners supported are assigned with general function
codes specified by Modbus-TCP.

Function Name

Code

Description

Read Coil Status

01h

Run/Stop(status), Lock(status), Swing(status), Alarm, Filter
Sign(status), Mode Lock(status), Wind Flow Lock(status)

Read Holding Registers

03h

Operation Mode(status), Fan Speed(status),
Room Temperature, Error Code,
Set Room Temperature(status),
Set Lower Temperature(status),
Set Upper Temperature(status),
User Mode(status)

Force Single Coil

05h

Run/Stop(setting), Lock(setting), Swing(setting),
Filter Sign Reset, Mode Lock(setting),
Wind Flow Lock(setting)

Preset Single Registers

06h

Operation Mode(setting), Fan Speed(setting),
Set Room Temperature(setting),
Set Lower Temperature(setting),
Set Upper Temperature(setting),
User Mode(setting)

64 Modbus