Troubleshooting

- Problem : The indoor unit is not found when checking whether the indoor unit is connected or not by

using the Web Server function.
→ If normal, the indoor units are displayed on the Web Server as many as the number of

the installed indoor units.

- Expected cause : The IP address and the Gateway address of the BACnet Gateway are not

correctly set.
The LAN cable is used incorrectly
The polarity between the PI 485 and the Gateway is changed

- Diagnosis

Are all indoor

units not found?

Perform the PING test
at the command prompt
window

NO

Does the LG-NET LED

of the BACnet Gateway

blinks?

Use the PMNFP14A1M by

checking the model name

of the PI485.

YES

Is it not searched for

each outdoor unit?

NO

NO

Do LED 02G and

03G of the PI485 of the said

outdoor unit keep

blinking?

YES

YES

YES

NO

Is it not searched for

each outdoor unit?

YES

Fail

YES

Check the
communication polarity
and short/open between
the PI 485 and the
BACnet Gateway and
check the setting of the
indoor unit address

Check the IP address and the
Gateway address of the
BACnet Gateway. Check
whether the LAN cable is
correct or not (direct cable
when the hub is used, cross
cable when the hub is not
used). Check whether the IP
of the PC can communicate
with the Gateway or not (It is
possible to communicate only
when the first three digits of
the private IP are same)

If it is abnormal after resetting
the BACnet Gateway,
consider whether to replace
the BACnet Gateway or not

Check the A/B polarity
between the said PI485 and
the Gateway. Check the
number of the outdoor unit
and the number of the PI485.

Recheck the setting of the
indoor unit address Make
sure that the communication
of the indoor/outdoor unit is
normal.

Check the said PI485
connection and the DIP switch.
Check whether the
communication of the
indoor/outdoor unit is normal
or not and check the setting of
the indoor unit address

90 BACnet Gateway