Detailed Explanation of Object

4) Lock (setting)

Point number: 3
Object name: LockCommand_XXX (XXX: A/C unit address)
Object type: Binary Output
Meaning: This object is used to set the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)

5) Lock (status)

Point number: 4
Object name: LockStatus_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is used to monitor the Lock of the A/C's control authority.
Present_Value property:
ACTIVE: Lock (Restricted)
INACTIVE: Unlock (Not restricted)

6) Filter Sign

Point number: 5
Object name: FilterSign_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is used to monitor the status of the filters for vent.
Present_Value property:
ACTIVE: Filter sign information is turned ON.
INACTIVE: Filter sign information is OFF.
Remarks: This object supports the Intrinsic Reporting function. When the Present_Value property

changes, the corresponding Event will be transmitted if the Event has been registered.

7) Filter Sign Reset

Point number: 6
Object name: FilterSignReset_XXX (XXX: A/C unit address)
Object type: Binary Value
Meaning: This object is used to reset the vent°Øs limit indication.
Present_Value property:
INACTIVE: Filter indication information is reset.
Remarks: 1. During a read operation of the Present_Value property, the Fliter Limit Sign Reset will

be always the same value as the Filter Limit Sign object.

2. Only if INACTIVE is written to the Present_Value property during a write operation,

the filter sign information resets ON signs and nothing will be executed even if
ACTIVE is written.

3. This object supports the Intrinsic Reporting function. When the Present_Value

property changes, the corresponding Event will be transmitted if the Event has been
registered.

76 BACnet Gateway