11) swing (status), 12) fan speed (setting), 13) fan speed (status) – LG PQNFB17B0 User Manual

Page 78

Advertising
background image

Detailed Explanation of Object

11) Swing (Status)

Point number: 10
Object name: SwingStatus_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is to monitor the air direction of the A/C.
Present_Value property:
ACTIVE: Swing_On
INACTIVE: Swing_Off

12) Fan Speed (Setting)

Point number: 11
Object name: FanSpeedCommand_XXX (XXX: A/C unit address)
Object type: Multistate Output
Meaning: This object is to set the airflow of the A/C.
Present_Value property:

Remarks: The A/C will disregard the command which the object which can't select the operation mode.

Therefore, controlled/monitored system shouldn't use the object which can't select the
operation mode.

13) Fan Speed (Status)

Point number: 12
Object name: FanSpeedStatus_XXX (XXX: A/C unit addresss)
Object type: Multistate Input
Meaning: This object is to monitor the airflow of the A/C.
Present_Value property:

Remarks: Present_value property will be set to "1:Low" as the default result if the property has

not been set in the past.

Indoor

Vent

1:

Low

Low

2:

Middle

High

3:

High

Super High

4:

Auto

Auto

Indoor

Vent

1:

Low

Low

2:

Middle

High

3:

High

Super High

4:

Auto

Auto

78 BACnet Gateway