Detailed Explanation of Object

18) User Mode (Setting)

Point number: 17
Object name: UserModeCommand_XXX (XXX: A/C unit address)
Object type: Multi-state Output
Meaning: This object is used to set the basic operation mode in vent and also additional

operation mode (quick fresh, energy efficiency, and heating).

Present_Value property:
1: Quick
2: Saving
3: Heater
Remarks: This object is for vent only, and will not apply if the property has not been set in the past.

19) User Mode (Status)

Point number: 18
Object name: UserModeStatus_XXX (XXX: A/C unit address)
Object type: Multi-state Input
Meaning : This object is used to monitor the basic operation mode in vent
Property_Value property:
1: Quick
2: Saving
3: Heater
Reamark : This object is for vent only, and will not apply if the property has not been in the past.

20) Set Temperature (status)

Point number: 19
Object name: SetTempStatus_XXX (XXX: A/C unit address)
Object type: Analog Output
Meaning: This object is used to monitor the set temperature of the A/C's control authority.
Present_Value property:
Temperature(°C)
Remarks : This object is for indoor units only, and reports the room temperature data measured
by the indoor units.

21) Accumulator Power Distribution (status)

Point number: 20
Object name: AccumPowerStatus_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor the accumulator power distribution of the A/C's control
authority.
Present_Value property:
Range is 0 to 255 (Power Distributiion : count * 100Watt)

80 BACnet Gateway