60 bacnet gateway – LG PQNFB17B0 User Manual

Page 60

Advertising
background image

Objects (BACnet/IP)

Point

No.

Name

ObjectName

Product Name

(XXX : Unit address)

Object

Type

Unit

Inactive

Active

Text-0

Text-1

Text-2

Text-3

Text-4

Text-5

21

Fire Alarm (Status)

FireAlarmStatus_XXX

BI

Stop

Run

22

Set Humidify (Setting)

SethumidifyCommand_XXX

AV

40~60

23

Set Humidify (Status)

SetHumidifyStatus_XXX

AI

40_60

24

Humidify (Setting)

HumidifyCommand_XXX

BO

Stop

Run

25

Humidify (Status)

HumidifyStatus_XXX

BI

Stop

Run

26

Auto Ventilation (Setting)

AutoVentCommand_XXX

BO

Stop

Run

27

Auto Ventilation (Status)

AutoVentStatus_XXX

BI

Stop

Run

28

Supply Temperature (Status)

SupplyTempStatus_XXX

AI

-127~127

29

Outdoor Temperature (Status)

OutdoorTempStatus_XXX

AI

-127~127

30

Mix Temperature (Status)

MixTempStatus_XXX

AI

-127~127

31

Supply Humidity (Status)

SupplyHumidifyStatus_XXX

AI

30~90

32

Outdoor Humidity (Status)

OutdoorHumidifyStatus_XXX

AI

30~90

33

Ventilation Humidity (Status)

VentHumidifyStatus_XXX

AI

30~90

34

CO2 Value (Status)

CO2ValveStatus_XXX

AI

0~255 (Real Value = Value*10, Example : In case Value is 20, CO2 is 20*10=200ppm)

35

Humidify Unit (Status)

HumidifyUnitStatus_XXX

BI

Stop

Run

36

Heater Unit (Status)

HeaterUnitStatus_XXX

BI

Stop

Run

37

Ventilation FAN (Status)

VentFANStatus_XXX

BI

Stop

Run

38

Supply FAN (Status)

SupplyFANStatus_XXX

BI

Stop

Run

39

Current OA Damper (Status)

CurOADamperStatus_XXX

AI

0~90

40

Current EA Damper (Status)

CurEADamperStatus_XXX

AI

0~90

60 BACnet Gateway