Installing a power supply – HP Integrity rx4610 Server User Manual
Page 34

Chapter 3
Installing Fans and Power Supplies
26
Figure 3-4. Removing a Power Supply
3. Pull the power supply straight forward, out of the chassis. Set it aside.
Installing a Power Supply
The power supply bay should not be vacant for more than five minutes when
server power is on. Disruption of the airflow may cause system cooling to fall
below acceptable levels. To install the new power supply, complete the following
procedure:
1. Remove the new power supply from the protective packaging, and place it
on an antistatic surface.
2. Record the model and serial numbers of the power supply in your
equipment log.
3. With the handle in the open position (pulled down), slide the replacement
power supply into the power supply bay until it stops.
4. Rotate the handle up and in to lock the power supply into place.
5. Check the new power supply LEDs to verify proper functioning.