HP Modular Cooling System User Manual

Page 12

Advertising
background image

Web interface 12

Indicators Meaning

Operator display alarm message Water flow Low
Web interface alarm message

Water flow Low

Condition

No or low water flow

Modules Water

group

SNMP notification

Warning

Type of message

Warning

Solution:
Verify the water supply.
Water temperature input is out of range

Indicators Meaning

Operator display alarm message Water Temp. In Failed
Web interface alarm message

Water Unit Temperature Input Out of Range

Condition

Water temperature sensor is not working properly (possible open circuit)

Sensors

Water group sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify the water supply.

2.

Verify whether the water temperature is below or above the water temperature expected range.

3.

Contact your building supervisor.

4.

Contact HP, or see the HP website (

http://www.hp.com

).

Water temperature output is out of range

Indicators Meaning

Operator display alarm message Water Temp. Out Failed
Web interface alarm message

Water Unit Temperature Output Out of Range

Condition

Water temperature sensor is not working properly (possible open circuit)

Sensors

Water group sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify the water supply.

2.

Verify whether the water temperature is below or above the water temperature expected range.

3.

Contact your building supervisor.

4.

Contact HP, or see the HP website (

http://www.hp.com

).

Water flow sensor is not working properly

Advertising