HP Modular Cooling System User Manual

Page 14

Advertising
background image

Web interface 14

Indicators Meaning

Sensors

Air temperature sensors

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify that nothing is blocking the heat path.

2.

Verify that the server is loading.

3.

Adjust the Temperature Difference for Heat Load Warning in the Advanced tab (on page

28

).

Heat overload condition (High Temperature Threshold field)

Indicators Meaning

Operator display alarm message Temperature too high
Web interface alarm message

Temperature too high

Condition

Heat overload condition

Modules or sensors

Average server air temperature is above the temperature assigned in the

web interface Intake Temp tab High Temperature Threshold field

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Verify the water inlet temperature.

2.

Verify that the flow matches the specifications required for heat load.

3.

Adjust the temperature assigned in the web interface Intake Temp tab High Temperature Threshold
field.

Leakage detected

Indicators Meaning

Operator display alarm message Leakage Detected
Web interface alarm message

Leakage Detected

Condition

Leak is detected

Modules or sensors

Leakage detector actuated

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Open the rack doors.

2.

Power down the rack-mounted components.

3.

Turn off the water to the MCS unit.

4.

Locate and correct the leak.

Communication failure

Advertising