Alarms/warnings tab – HP Modular Cooling System User Manual

Page 27

Advertising
background image

Web interface 27

NOTE:

If using Mozilla, you can manually import the file into the browser by clicking

File>Preferences>Certificates>Privacy & Security>Manage Certificates>Authorities>Import.

Alarms/Warnings tab

This screen enables the Admin to change alarm and warning settings for the management module.

To change the alarm and warning settings:

1.

Select to enable or disable the alarm relay from the Alarm Relay radio buttons. This setting affects all
alarms and warnings, except for the Server Intake Temperature.

o

Select Enable to allow the alarm relay when a temperature alarm is generated.

o

Select Disable to not allow the alarm relay when a temperature alarm is generated.

2.

Select to enable or disable the audible alarm from the Audible Alarm radio buttons. This setting
affects all alarms and warnings, except for the Server Intake Temperature.

o

Select Enable to allow the audible alarm to sound when an alarm is generated.

o

Select Disable to not allow the audible alarm to sound when an alarm is generated.

3.

Select to allow the alarm to be reset (which also resets the audible alarm and alarm relay)
automatically (Auto) or manually (Manual) from the Alarm Reset radio buttons. This setting affects all

alarms and warnings, except for the Server Intake Temperature.

o

Select Auto to allow the alarm to be turned off automatically if the condition returns to a valid
range after an alarm is generated.

o

Select Manual to allow the alarm to be turned off by clicking Clear Alarms in the Setup>General
menu. The alarm can also be cleared by pressing the C key on the management module after

any alarm is generated.

4.

Select the checkbox to deactivate the scheduled alarms for trap receivers 1 through 4.

5.

Do one of the following:

o

Click Save Settings to save the information.

o

Click Cancel to undo the changes.

Advertising