Web interface 15

Indicators Meaning

Operator display alarm message Comm. Failure I²C
Web interface alarm message

Comm. Failure I²C

Condition

Management module cannot communicate with the MCS unit sensors

Modules or sensors

Any module or sensor

SNMP notification

Critical

Type of message

Alarm

Solution:
Power cycle the management module. If the alarm message continues to appear, replace the

management module with a CSR part. For more information on CSR parts, see "Replaceable parts and

maintenance and service information (on page

54

)."

Temperature below threshold (Low Temperature Threshold field)

Indicators Meaning

Operator display alarm message Temperature Too low
Web interface alarm message

Temperature too low

Condition

Average server air temperature is lower than the temperature assigned in
the web interface Intake Temp tab (on page

22

) Low Temperature

Threshold field

Sensors

Air temperature sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify water flow matches specifications required for heat load.

2.

Verify whether the water temperature is below the expected range.

3.

Adjust the temperature assigned in the web interface Intake Temp tab (on page

22

) Low

Temperature Threshold field.

4.

Contact your building supervisor.

Temperature above threshold (Warning Temperature Threshold field)

Indicators Meaning

Operator display alarm message Temperature Warning
Web interface alarm message

Temperature Warning

Condition

Average server air temperature is above the temperature assigned in the

web interface Intake Temp tab (on page

22

) Warning Temperature

Threshold field

Modules or sensors

Air temperature sensor

SNMP notification

Warning

Type of message

Warning

Solution: