HP Modular Cooling System User Manual

Page 13

Advertising
background image

Web interface 13

Indicators Meaning

Operator display alarm message Water flow Sensor ?
Web interface alarm message

Water flow Sensor Value Out of Range

Condition

Water flow sensor is not working properly

Sensor Water

group

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify the water supply.

2.

Contact HP, or see the HP website (

http://www.hp.com

).

Water flow valve is closed

Indicators Meaning

Operator display alarm message Water Valve ?
Web interface alarm message

Water Valve Failed

Condition

Water flow valve is closed and water flow is detected

Modules Water

group

SNMP notification

Warning

Type of message

Warning

Solution:

1.

Verify the water valve is closed.

2.

Contact HP, or see the HP website (

http://www.hp.com

).

Leak detector sensor is not working properly

Indicators Meaning

Operator display alarm message Leak detector?
Web interface alarm message

Leak detector Failed

Condition

Leak detector sensor is not working properly

Sensors

Leak detector sensor

SNMP notification

Warning

Type of message

Warning

Solution:
Contact HP, or see the HP website (

http://www.hp.com

).

Uneven heat load

Indicators Meaning

Operator display alarm message Heat Load?
Web interface alarm message

Heat Load Warning

Condition

Measured air temperature values dramatically different from top to bottom