2940 air adjust cab controller operation – Yetter 2940 Short Floating Air Adjust Residue Manager User Manual

Page 52

Advertising
background image

52

2940 AIR ADJUST

CAB CONTROLLER OPERATION

3.4.

Main Menu: This screen will allow you to navigate to the setup and service screens. Selecting
EXIT will return you to the main operating screen.

3.5.

Setup: Currently this screen has one option to select the (Dump Valve Delay).

3.6.

Dump Valve Delay: This screen allows you to adjust the dump valve delay time. Press the
ENTER button to go into the edit mode, and then adjust the time with the SCROLL UP/DOWN
buttons. The time value will have .25 second resolution and will be adjustable from 0-60 seconds.
Pressing ENTER again will exit the edit mode. Generally, no more than 2.5 seconds is needed.

Setting the Dump Valve Delay:

a. Ensure all dump valves and harnesses are plugged in securely, and dump valves are functioning

properly.

b. Adjustments will be made in increments of .25 seconds.
c. Proper action should be: when raised, row cleaners come up and stay. When lowered, dump valves

will fire, row cleaners should come to ½ travel (or to when the linkage is parallel), at which time the
dump valves will close, then row cleaners will fall back to preset pressures slowly.

d. Access the dump valve delay screen on your cab controller.
e. Adjust to .5 second delay, revert to home screen.
f.

Press the dump I button and observe row cleaners, it is best to have a second person looking as
well.

g. Adjust as needed, if they pause just above center, more time is needed. If they fall farther than

center, less time is needed.

h. When the correct setting is achieved, exit the dump valve delay screen and revert back to the home

screen.

3.7.

Service: This screen has (3) selections to choose from, HOUR METERS, MAINTENANCE, and
FAULT STATUS.

3.8.

Hour Meters: This screen will contain (2) hour meters, air compressor hours, which only
increments if the compressor is on, and total system hours, which only increments if the air system
is enabled (AIR ON). There will also be a field that shows duty cycle; this is a cumulative value
calculated by dividing compressor hours by system hours.

3.9.

Maintenance: This screen is static and has a text description indicating basic maintenance info.

3.10.

Fault Status: J1: This screen contains real time read outs of command and feedback voltage

readings for each pin present in the connector labeled J1.

3.11.

Fault Status: J2: This screen contains real time read outs of command and feedback voltage
readings for each pin present in the connector labeled J2


3.12.

Fault Status: J3: This screen contains real time read outs of command and feedback voltage
readings for each pin present in the connector labeled J3

3.13.

Fault Status: J4: This screen contains real time read outs of command and feedback voltage
readings for each pin present in the connector labeled J4

3.14.

Warning – Compressor Run Time: This screen will be displayed if the compressor has been
running continuously for 15 minutes.

Evaluate the system for leaks or other issues before

continuing. When problems are fixed, press enter to clear the screen and resume normal
operation.

3.15.

Warning – Check Fault Screens: If a fault is detected, this screen will be displayed. Contact a
service representative at Yetter, and have the fault screens ready, to review voltage readouts for
diagnostics. This warning will remain displayed until the enter button is pressed.

Advertising