Firmware updates, Commissioning – Outback Power Systems GS3548E Operators Manual User Manual

Page 14

Advertising
background image

Commissioning

12

900-0145-01-01 Rev A

Firmware Updates

IMPORTANT:

All inverters will shut down during firmware updates. If loads need to be run while
updating the firmware, bypass the inverter with a maintenance bypass switch.
Communication cables must remain connected and DC power must remain on.
Interrupted communication will cause the update to fail and the inverter(s) may not
work afterward. Inverters automatically update one at a time beginning with Port 1.
Each requires about 5 minutes.

Updates to the Radian’s internal programming are periodically available at the OutBack website

www.outbackpower.com. If multiple inverters are used in a system, all units must be upgraded at the
same time. All units must be upgraded to the same firmware revision.

If multiple stacked Radian inverters are used with different firmware revisions, any inverter with a
revision different from the master will not function. (See the stacking section on page 36.) The MATE3

will display the following message:
An inverter firmware mismatch has been detected. Inverters X, Y, Z

1

are disabled. Visit

www.outbackpower.com for current inverter firmware.

NOTES:




















1

The port designations for the mismatched inverters are listed here.

Advertising