Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS3548E Operators Manual User Manual

Page 55

Advertising
background image

Troubleshooting

900-0145-01-01 Rev A

53

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Low charge rate.

Charge complete or nearly
complete.

Check the DC voltage and charging stage using the MATE3, if
present. Confirm with DC voltmeter.

MATE3’s DC meter reads
significantly higher than actual

battery voltage.

Check the DC voltage on the inverter’s DC terminals. If different
from the MATE3 reading, the inverter could be damaged.

Otherwise, check the DC voltage on batteries with a voltmeter. If

different from the reading on the inverter, this could be a DC

connection problem.

High output loads.

If total loads and charge exceed the AC input setting, charge rate

decreases to give priority to the loads. Turn off some of the

output loads and test the charge rate again.

High temperature.

The inverter will reduce the current rate for charging and other

activities if the internal temperature exceeds a certain level.
Check temperature readings and allow the inverter to cool if

necessary. (See page 59.) External cooling may also be applied.

Will not charge.

No AC input.

See “Will not connect to AC” category.

Charger set to

Off.

MATE3 system display only: Check the

Charger Mode screen with

the CHARGER

hot key and set to On or Auto. (If this setting was

intentional, then no action is required.)

Grid Zero mode in use.

MATE3 system display only: The charger is inoperative in

Grid Zero

mode. (If this setting was intentional, then no action is required.)

Unusual voltage on
AC hot input line.

Inverter has not synchronized
with input source.

MATE3 system display only: The

AC In reading accessed by the

Inverter soft key may be erratic or inaccurate after initial

connection until the inverter has synchronized with the AC

source. This may require a short time.

Unusual voltage on

hot or neutral output

line.

System neutral and ground may

not be bonded.

Test “L” and “N” OUT test points with AC voltmeter. (See page 51.)

These measurements should give full voltage. Test neutral and

ground connections. This measurement should read zero volts.

Any other result means neutral and ground are not bonded
correctly. (If bonding is not required or prohibited by national or

local codes, then no action may be required.)

Inverter does not
perform the Offset

function when

expected.

Incorrect input mode.

Offset does not function in

Generator, UPS, and Backup modes.

Specific mode only offsets

under particular conditions.

Support mode will perform the Support function based on load.

This may appear as Offset without reaching the reference voltage.
Grid Zero mode will perform Offset based on the DoD Volts
setting. Other reference voltages are not used.

Reduced power sold
to the utility grid.

AC source voltage is driven high
when the inverter sells large

amounts of power.

When the inverter senses a rise in grid voltage while selling, it
reduces the sell current, to avoid forcing the voltage to

unacceptable levels. Check AC input voltage while selling. The

inverter may be operating correctly.

High temperature.

The inverter will reduce the current rate for selling and other
activities if the internal temperature exceeds a certain level.

Check temperature readings and allow the inverter to cool if

necessary. (See page 59.) External cooling may also be applied.

Advertising
This manual is related to the following products: