Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS3548E Operators Manual User Manual

Page 54

Advertising
background image

Troubleshooting

52

900-0145-01-01 Rev A

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

One or more
inverters will not

invert while others

do (in multi-inverter

system).

Unit is slave and is in Power
Save mode.

MATE3 system display only: Check Power Save levels in
the

Inverter Stacking menu and test with loads. Determine if the

inverter comes on at the appropriate levels. (If this setting was

intentional, then no action is required.)

Will not connect to

the AC source.

No AC input.

Check the AC voltage on the inverter’s input test points. (See
page 51.) If not present, the problem is external. If present, the

inverter could be damaged. Contact OutBack Technical Support.

4

AC source does not meet
requirements.

MATE3 system display only: Check the

Last AC Disconnect screen

(using the AC INPUT

hot key and the Discon selection) for the

reason for disconnection. If the unit never originally connected,

check the

Warning menu (using the Inverter soft key from the

Home screen). Confirm source voltage and frequency.

AC source meets requirements

but is “noisy” or irregular.

MATE3 system display only: The

Generator input mode can accept

irregular AC power. Select that mode for that input.

Inverter was manually set to
disconnect from AC.

MATE3 system display only: Change the AC Input Control setting
from

Drop to Use with the AC INPUT hot key. (If this setting

was intentional, then no action is required.)

Grid use function has
disconnected from AC.

MATE3 system display only: If activated prematurely, check both
the MATE3’s

Grid Use Time settings and the MATE3 clock settings

in the

System menu. (If this setting was intentional, then no

action is required.)

High Battery Transfer

(

HBX) mode has disconnected

from AC.

MATE3 system display only: Check the AC INPUT hot key screen

to see if

HBX mode is in use. If activated prematurely, check the

settings of

HBX mode. (If this setting was intentional, then no

action is required.)

Mini Grid input mode has

disconnected from AC.

MATE3 system display only: Check the

Inverter part of the Settings

menu to see if

Mini Grid mode is in use. If activated prematurely,

check the settings of

Mini Grid mode. (If this setting was

intentional, then no action is required.)

Conflicting programming.

MATE3 system display only: Check to see if more than one of the
following are enabled:

Mini Grid, HBX, Grid Use Time. These have

conflicting priorities and only one can be used at a time.

Grid Tied mode has

disconnected from AC.

AC source does not meet requirements; see related entry under
“Will not sell power to the utility grid” (next page).

For only the B or C inverters on

a three-phase system: Power is

unacceptable on that phase.

Check the source voltage and frequency. If the AC source voltage

or frequency cannot be maintained on the B or C phases, the

inverters on those phases will return to inverting. This ensures
that a three-phase output is maintained to the loads. If the source

becomes acceptable, the inverters will connect to it again.

Conflicting AC sources. Priority
input is interfering with

secondary input.

If AC is present on the priority input, the inverter will not connect
to AC on the second input. This is true even if the first input is not

connected for other reasons (programming, low power quality).

4

See inside front cover of this manual.