Operation

42

900-0145-01-01 Rev A

In Table 4, instead of loads, the number on the far left of each line shows the master increased by one

rank. (This example is otherwise the same as Figure 13.)
The last line of the table shows the master increased to 3, which is the same as the rank of the highest

slave. However, this only activates the first of the three slaves. The master would need to be set to

rank 7 to activate all slaves.

Table 4

Changing Master Power Save Levels (GS7048E)

Master

Slave 1

Slave 2

Slave 3

Power

Save

Module

1

Module

2

Power

Save

Module

3

Module

4

Power

Save

Module

5

Module

6

Power

Save

Module

7

Module

8

0

On

Off

1

Off

Off

2

Off

Off

3

Off

Off

1

On

On

1

Off

Off

2

Off

Off

3

Off

Off

2

On

On

1

On

Off

2

Off

Off

3

Off

Off

3

On

On

1

On

On

2

Off

Off

3

Off

Off