Firmware Revision

This manual applies to inverter models GS7048E and GS3548E with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the
OutBack website www.outbackpower.com. See page 12.

Default Settings and Ranges

NOTE: Some items are retained at the present setting even when the inverter is reset to factory

defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface

Protection menu. These menus are bordered in the table with a double line of this style:

Table 16

Radian Inverter Settings

Field

Item

Default

Minimum

Maximum

INVERTER

Hot Key Inverter Mode

Off

On, Off, or Search

CHARGER

Hot Key Charger Control

On

On or Off

AC Input

Hot Key

AC Input Mode

Use

Drop or Use

Search

Sensitivity (see page 23 for increments)

10

0

250

Pulse Length

8 AC Cycles

4 AC Cycles

20 AC Cycles

Pulse Spacing

60 AC Cycles

4 AC Cycles

120 AC Cycles

AC Input and
Current Limit

Input Priority

Grid

Grid or Gen

Grid Input AC Limit

50 Aac

5 Aac

55 Aac

Gen Input AC Limit

50 Aac

5 Aac

55 Aac

Charger AC Limit

GS7048E

30 Aac

0 Aac

30 Aac

GS3548E

15 Aac

0 Aac

15 Aac

Grid AC Input
Mode and Limits

Input Mode

Grid Tied

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid, Grid Zero

Voltage Limit Lower

208 Vac

170 Vac

230 Vac

(Voltage Limit) Upper

252 Vac

232 Vac

290 Vac

Transfer Delay

1 second

0.12 seconds

4.0 seconds

Connect Delay

0.2 minutes

0.2 minutes

25.0 minutes

When Mini Grid
mode is selected:

Connect to Grid

48.0 Vdc

44.0 Vdc

64.0 Vdc

(Connect) Delay

10 minutes

2 minutes

200 minutes

When Grid Zero
mode is selected:

DoD Volts

48.0 Vdc

44.0 Vdc

64.0 Vdc

DoD
Amps

GS7048E

5 Aac

1 Aac

30 Aac

GS3548E

5 Aac

1 Aac

15 Aac

Gen AC Input
Mode and Limits

Input Mode

Generator

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid, Grid Zero

Voltage Limit Lower

208 Vac

170 Vac

230 Vac

(Voltage Limit) Upper

252 Vac

232 Vac

290 Vac

Transfer Delay

1 second

0.12 seconds

4.0 seconds

Connect Delay

0.5 minutes

0.2 minutes

25.0 minutes

If Mini Grid mode
is selected:

Connect to Grid

48.0 Vdc

44.0 Vdc

64.0 Vdc

(Connect) Delay

10 minutes

2 minutes

200 minutes

If Grid Zero mode
is selected:

DoD Volts

48.0 Vdc

44.0 Vdc

64.0 Vdc

DoD
Amps

GS7048E

5 Aac

1 Aac

30 Aac

GS3548E

5 Aac

1 Aac

15 Aac