Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS3548E Operators Manual User Manual

Page 57

Advertising
background image

Troubleshooting

900-0145-01-01 Rev A

55

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Inverter clicks

repeatedly. AC

output voltage rises

or drops to unusual

levels with every

click.

Inverter’s output has been

connected to its input. Voltage

shifts are the result of trying to
match its own voltage.

Disconnect the wires from the inverter’s AC input or AC output

terminals, or both. If the problem immediately disappears, it is an

external wiring issue. The inverter’s AC IN and AC OUT must
remain isolated from each other.

Low AC input voltage. Can be

caused by weak AC source, or

by faulty input connection.

Test AC hot and neutral input test points with an AC voltmeter.

(See page 51.) If low or fluctuating, this is an external problem.

A generator is connected to the

input terminals while the unit is

in the

Grid Tied input mode.

The inverter is not intended to sell power to a generator. The

selling activity will drive the generator voltage up to the

disconnection point. It will then reconnect to the generator and
try again. Change input modes, or move the generator to an

input with a different mode selected.

Unit reads AC input,

even though no

source is present.

Internal transfer relay may be

damaged. May be

accompanied by

AC Relay Fault

error and shutdown.

Disconnect AC input wires and turn inverter on. Test the AC input

and neutral test points with an AC voltmeter. (See page 51.) If

voltage appears there, the transfer relay may be jammed. Contact

OutBack Technical Support.

5

This problem is not common. If this

occurs, it will likely occur on only the Grid or Gen input — not

both.

False reading due to noise.

Electrical noise can cause false readings on the metering circuits

when no voltage is present. The readings are usually less than

30 Vac. If this is the case, no action is required.

Inverter hums loudly.

System display may

show messages for

high battery voltage,

low battery voltage,
or backfeed error.

Inverter output is being

supplied with an external AC

source that is out of phase.

Disconnect AC output wires. Turn the inverter off and then on. If

the problem clears, reconnect the AC output wires. If the

problem recurs when reconnected, an external AC source is

connected to the output.

Inverter has been incorrectly

stacked with another unit on

the same output. All units
come defaulted as master.

Check HUB ports and make certain the master inverter is plugged

into port 1.

MATE3 system display only: Check stacking settings in the

Inverter

Stacking menu. Only one master is allowed per system.

Generator, external
fan, etc. fails to start

when signal is

provided by AUX

output.

AUX output is not connected.

Test the generator or device to confirm functionality. Test the

appropriate AUX terminals with a DVM. (If the RELAY AUX

terminals are in use, test for continuity. If the 12V AUX terminals

are in use, test for 12 Vdc.) If the proper results are present when
the menu indicates the function is

On (and the device still does

not work), then there is an external connection problem. If the
proper results are not present with the function

On, the AUX

circuit may be damaged. Contact OutBack Technical Support.

5

Wrong AUX terminals have
been programmed.

MATE3 system display only: Confirm that the AUX menu that was
programmed matches the terminals that are in use. The

Auxiliary

Output menu programs the 12V AUX terminals. The Auxiliary
Relay
menu programs the RELAY AUX terminals.

Wrong AUX terminals are in use.

If generator or external device requires 12 Vdc, confirm the 12V

AUX terminals have been connected. The RELAY AUX terminals

do not provide voltage.

5

See inside front cover of this manual.

Advertising
This manual is related to the following products: