Compliance, Specifications – Outback Power Systems GS3548E Operators Manual User Manual

Page 68

Advertising
background image

Specifications

66

900-0145-01-01 Rev A

Compliance

RoHS: per directive 2011/65/EU

These inverter/charger models have grid-interactive functions. All models are

tested to comply with certain limits for acceptable output voltage ranges,

acceptable output frequency, total harmonic distortion (THD) and anti-islanding performance when
the inverter exports power to a utility source. The OutBack inverter/charger models listed in this

document are validated through compliance testing. The following specifications refer to exporting

power to a simulated utility source of less than 1% voltage total harmonic distortion (THD).

The THD of the root mean square (RMS) current is less than 5%.

The output of the Radian inverter exceeds the minimum power factor of 0.85 with a typical power factor of
0.96 or better.

The reconnection delay has a default setting of 1 minute. The grid-interactive default settings are
shown in the

Grid Interface Protection Menu portion of Table 16 on page 69.

The

Grid Interface Protection settings are adjustable. However, this is only available to operators with

installer-level access. The reason for this limitation is that there are firm rules concerning the

acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay

when exporting power back to the utility. The rules differ in different locations around the world,

although generally it is expected that the settings cannot be altered by the end user. For this reason,
the installer password must be changed from the default to get access to these settings.

See the

Grid Tied function on page 15 for more information.

To meet the standard AS4777.3 for installations in Australia, the acceptance settings shall not exceed

the following. The factory default settings meet these requirements.

Table 15

AS4777.3 Acceptance Settings

Minimum

Voltage

Maximum

Voltage

Minimum

Frequency

Maximum

Frequency

200 Vac

270 Vac

45 Hz

55 Hz