Additional Notes for the Radian GS7048E:

The GS7048A has two modules. The modules are controlled individually. The Power Save function

will activate one module at a time, making an additional 3.5 kW of power available for every load

increase of approximately 2.5 kW.
Figure 13 shows a system of four GS7048E inverters (the master and three slaves) in a parallel system

with a common load bus. The labels at the top indicate the ranking of each unit. The notations at the

bottom show how the units are activated in sequence as loads of approximately 2.5 kW are applied.

The first line shows little load and only the first module in Master is activated.

The second line shows load beginning to be applied. The second module in Master is activated.

The third line shows increasing load. The first module in Slave 1 is activated.

The fourth line shows even higher load. Slave 1 is completely activated.

In general, roughly 5 kW of loads are applied to fully activate an additional slave inverter.

In the example shown in Figure 13, an 8-kW load has been applied, fully activating the first slave.

In this example, loads of approximately 17 to 18 kW would be needed to turn on all inverters.

Figure 13

GS7048E Power Save Priority

Forcing Specific Slaves to be Active:
It is possible to raise the priority of a slave and force it to activate. This is done by setting the master
rank higher than that slave. However, the

Master Power Save Level scale is not the same as the Slave

level.

Slave level settings apply to the whole inverter. Master level settings are applied per module.

This means that increasing the master by one rank will only turn on one additional module. To

completely turn on a slave inverter, the master must be increased two ranks. See the next page.

On

Off

Off

Off

Off

Off

Off

Off

On

On

Off

Off

Off

Off

Off

Off

Module 1 Module 2

Module 1 Module 2

Module 1 Module 2

Module 1 Module 2

On

On

On

Off

Off

Off

Off

Off

On

On

On

On

Off

Off

Off

Off

Minimal load

approx. 5 kW

approx. 2.5 kW

approx. 7 to 8 kW

Master

Master Power Save

= 0

Slave 1

Slave Power Save

= 1

Slave 2

Slave Power Save

= 2

Slave 3

Slave Power Save

= 3