4.5.1 AS-i / PROFIBUS gateway

Fig. 7

No.

Designation

1

Status LEDs

2

PROFIBUS connector

3

Digital display

4

If a "fault" is indicated, the number
of the faulty slave and the reason
for the fault are shown by a dot

5

Buttons for manual control

6

AS-i power supply

7

AS-i circuit

NOTE !
- Never connect slaves or repeaters to the power supply cable (ASI PWR).
- Never connect AS-i power supplies or other masters to the AS-i connecting

cable.

Status LEDs

Meaning / cause

power

- The master is receiving sufficient power

Profibus

- LED on: The gateway is assigned to a PROFIBUS master
- LED off: The gateway is not assigned to a PROFIBUS master

fault

- If a "fault" is indicated, the number of the faulty slave and the

reason for the fault are shown by a dot

U AS-i

- The AS-i circuit is receiving sufficient power

AS-i active

- Normal operation (the LED blinks to indicate B slaves)

prg enable

- Addresses can be programmed automatically

prj mode

- The AS-i master is in configuring mode